AEROFLEX Closed Cell Elastomeric Thermal Insulation

AVERAGE PHYSICAL PROPERTIES
AEROFLEX INSULATION
TEST METHOD***
Cell structure
Closed cell
-
Density(pound/cubic feet) (gm/cubic cm)
4-6 (0.06 -0.10)***
ASTM D 1667
Thermal Conductivity
BTU. in/sq. ft hr.°F (W/m. K)
Mean Temp.
- 4°F
(-20°C)
32°F
(0°C)
75°F
(24°C)
90°F
(32°C)
104°F
(40°C)
ASTM C 177
JIS A 1412 - 1989
DIN 52613
K. Value
0.23
(0.034)
0.24
(0.035)
0.26
(0.038)
0.27
(0.039)
0.28
(0.040)
Service Temperature Limit****
-70°F to 257°F
(-57°C to 125°C)
Aeroflex starts to become harder at -57°C and can be serviced down to -200°C
Water Vapor Permeability (Kg/Pa.s.m)
0.15 perm - in. (0.22 x 10*)
ASTM C 355, E 96*****
µ>/=4,000
DIN 52615
Water Absorption (% by weight)
3
ASTM D 1056
Ozone Resistance
Excellent
ASTM D 1056
Thermal Stability
(% shrinkage)
7 days 200°F
5
ASTM C 534
7 days 200°F
6
Flammability & Smoke Density******
Self-extinguishing
ASTM D 635
Class V 0
UL - 94
Class 5.3
EMPA*******
Non - Flammable
JIS K 6911
Weather and Ultraviolet Resistance
Good
-
Copper Corrosion
Negligible
-
Odor
Negligible
-
Flexibility
Excellent
-
Elongation
Excellent
-

Note :
* The physical properties of Aeroflex Closed Cell Insulation represent typical average values obtained in accordance with accepted test methods.
** Also tested by other standards : DIN, JIS, SISIR and others.
*** For thickness ranging from 25 mm and above, Density 3-5 lbs/cubic ft (0.05 - 0.08 gm/cubic cm)
**** At - 57 °C flexible Aeroflex Closed Cell Insulation becomes harder and as temperature drops below - 75 °C it becomes increasingly brittle : however this hardening characteristic does not affect thermal efficiency and water vapor permeability. On the heating cycle, Aeroflex Closed * Cell Insulation will withstand temperatures upto 125 °C. For butt joint and seams contacted with Aeroseal Adhesive, the limited temperature is upto 100 °C.
***** Water vapor Permeability of Aeroflex insulation is tested according to ASTM E 96 procedure E - Desiccant method at 100 °F (37.8 °C)
****** Aeroflex Closed Cell Insulation is made of specially compounded elastomeric materials for self extinguishing. The flammability of this insulation has been tested by exposing samples of 6" x 2" x 1/2" thickness to the procedures of ASTM D 635 test method entitled " Flammability of Plastics and Cellular Plastics". During this test, the sample is positioned horizontally. And for the procedure of UL - 94 the sample size of 1/2" x 1/2" x 5" is positioned vertically. The test method is not intended as a criterion of fire hazard. It can be of considerable value in comparing flammability to different materials.
******* EMPA' : Swiss Federal Laboratories for Materials Testing and Research.


Complete cross linking closed cell structure
Low density 4-6 lbs/cubic ft
(0.06-0.10 g/cubic cm)
ASTM D 1667
Low thermal conductivity ASTM C 177

Wide temperature continous service ranging from - 57 °C to 125 °C.
Low water absorption ASTM D 1056, Low water vapor permeability ASTM E 96
Excellent ozone and weather resistance ASTM D 1171. D 1149

Self extinguish ASTM D 635 flame proof ASTM E_84
No problem for copper pipe corrosion even after a long period of service
CFCs free product - Ozone friendly product.